Skip to content
BITMAIN
ANTRACK AR30 — image 1 of 5
ANTMINER

FUTURESANTRACK AR30

Function
BTC/BCH/BSV SHA256
Specifications
1Set | 200kW | 20 units ANTMINER (U2 Hydro)
Cooling
Hydro-Cooling
Weight
780 kg
Price
$16,000
Shipping Date
Shipping from November 2026

For orders of 100 units or more, use Bulk Order.

| Specifications


Product Glance Value
Model ANTRACK
Version AR30
Capacity 20 units ANTMINER (U2 Hydro) or 14 units ANTMINER (T-type Hydro)
Miner maximum load,kW 200
Total load, kW 207
Detailed Characteristics Value
Part 1: Mining Cabinet  
Hardware Configuration  

Size (Length*Width*Height), mm (without package)

1,000*1,200*2,300

Size (Length*Width*Height), mm (with package)

1,070*1,380*2,400

Net weight, kg (without package)

670

Gross weight, kg (with package)

780

Network connection mode

RJ45 Ethernet 10/100M
Power Supply  
Power supply AC Input voltage, Volt(1-1) 380~480V AC
Power supply AC Input Frequency Range, Hz 50~60
Power supply AC Input current, Amp(1-2) 315 @ 380V
249 @ 480V
Water pump  

Rated power, kW

7.5

Noise, dBA@1m

79
Lift, m 73
Size (Length*Width* Height), mm 618*248*300
Plate heat exchanger  
Maximum heat exchange power, kW 200
Size (Length*Width* Height), mm 490*235*250
Diameter of water pipe connector, mm

DN50

Environment Requirements  
Coolant inlet temperature, °C -20~45
Water flow, L/min 320~350
Water pressure, bar ≤3.5
Working fluid(1-3) Organic Antifreeze (10%)
Installation distance, m(1-4) ≤5
Liquid PH 7.8~8.5
Storage temperature, °C -40~70
Operation humidity(non-condensing), RH 10~90%

Notes:

(1-1) Caution: Wrong input voltage may probably cause miner damaged.

(1-2) Three-phase AC input.

(1-3) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.

(1-4) The maximum distance between mining cabinet and external cooler.